UPS Runtime Calculator

This calculator works out UPS runtime from its battery bank and actual load. The estimate applies usable discharge and UPS efficiency to the internal battery bank before dividing by connected watts. Replace the example values with information from your own label, bill, drawing, product sheet or land record. Use actual load and the UPS maker's discharge curve because small sealed batteries lose effective capacity at high rates. The formula and every editable assumption remain visible so the result can be checked before it is used for planning. Keep the values and result together when you compare or share this planning scenario.

Updated 9 August 2026Use for planningFormula and steps shown
01

Enter your details

Your values

Every input includes a simple explanation.

Simple wordsFormula shownPrivate inputs
Simple viewUsing editable example assumptions for technical settings.

Private: calculations run in your browser. Saved scenarios, preferred electricity rate and land state stay on this device.

Worked UPS-runtime examples

Why VA alone cannot tell you the runtime

Runtime comes from battery energy and the connected watts after usable-discharge and conversion losses. These linear examples teach the chain; the UPS maker's discharge curve remains the better check for a specific model.

Illustrative calculations. Replace every value with evidence for your equipment or project.
ExampleInputsVisible workingAnswer
Two 12 V, 9 Ah batteries80% usable, 80% efficiency, 120 W load12 × 9 × 2 × 0.80 × 0.80 ÷ 1201.15 hours
Two 12 V, 18 Ah batteries80% usable, 80% efficiency, 200 W load12 × 18 × 2 × 0.80 × 0.80 ÷ 2001.38 hours
One 24 V, 100 Ah bank50% usable, 85% efficiency, 500 W load24 × 100 × 0.50 × 0.85 ÷ 5002.04 hours
Get a useful answer

How to use this calculator

  1. Step 1. List only the appliances needed during a power cut and use their running watts.
  2. Step 2. Start with the simple result, then open advanced assumptions for losses, surge and usable battery share.
  3. Step 3. Check continuous and surge ratings, battery compatibility and safe installation with the product sheet or installer.
What can change the answer

Check these details

01

Motors and compressors can need extra power when they start.

02

Battery age, temperature and a high discharge rate can reduce delivered energy.

03

Use this as a planning range. Confirm continuous rating, peak rating and battery compatibility with the manufacturer and a qualified installer.

Understand your result

What this answer means

Read the meaning first, verify the important details, then avoid the most common planning error.

What it means

The estimate applies usable discharge and UPS efficiency to the internal battery bank before dividing by connected watts.

What to check next

Use actual load and the UPS maker's discharge curve because small sealed batteries lose effective capacity at high rates.

Common mistake

The VA printed on a UPS is not battery energy and cannot by itself predict minutes of runtime.

Sources and method

Sources used for this calculator

Documented dimensional-analysis formulasGharGanit editorial methodologyFormulas are derived from units and expose every editable efficiency, density, dry-volume and wastage assumption. Reviewed 2026-07-16.Measures relating to safety and electric supply regulationsCentral Electricity Authority, Government of IndiaSupports the safety boundary shown on backup, inverter, pump and EV calculations; it is not used to invent equipment performance. Reviewed 2026-07-19.
Official verification links

Check the official context

These independent government and standards resources help you verify the inputs or decision. Inclusion is not an endorsement.

Browse all 72 verified links
Learn before deciding

Useful next reading

Read the inverter and battery guide Understand 150 Ah backup time Compare watts, VA and Ah Explain lower real backup
Calculator revision

Version 1.2

Updated 9 August 2026. Changes listed here describe this calculator release; they are not invented historical entries.

  • Matched search metadata to the exact calculation task.
  • Added a task-specific example using label, bill or measured inputs.
  • Kept rates, losses and operating assumptions editable and visible.
Read the correction process